Table of Contents

Task D-13 Installs water-based systems

Task Descriptor

Sprinkler fitters install water-based systems in institutional, commercial, industrial and residential buildings. These systems use water as an integral part of the suppression/control agent. They primarily remove heat from the fire to suppress or control the fire.

D-13.01 Installs wet pipe systems

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-13.01.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-13.01.02P

determine and measure locations of mains and branch lines locations of mains and branch lines are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.01.03P

determine and measure locations and requirements of components locations and requirements of components are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.01.04P

determine and measure locations of auxiliary drains and requirements for valves locations of auxiliary drains and requirements for valves are determined and measured according to NFPA standards to ensure accessibility for servicing and testing

D-13.01.05P

measure and fabricate piping piping is measured and fabricated for installation according to drawings, AHJ, NFPA standards and site conditions

D-13.01.06P

measure and install return bends and flexible drops return bends and flexible drops on wet pipe systems are measured and installed according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.01.07P

connect piping to water supply piping is connected to water supply using methods according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.01.08P

install auxiliary devices auxiliary devices are installed according to NFPA standards to ensure accessibility for servicing and testing

D-13.01.09P

measure and install alarm valve trim alarm valve trim is measured and installed according to manufacturers’ specifications and NFPA standards

D-13.01.10P

pressure test wet pipe system wet pipe system is pressure tested according to NFPA standards and AHJ

D-13.01.11P

install signage and identification signage and identification are installed according to NFPA standards and AHJ

Range of Variables

components include: fire department connection, test connections and drains, sprinklers, alarm devices, control valves, alarm check valves, water flow alarm devices, relief valves, valves, flow switches, riser manifolds, air vents

piping includes: risers, starter pieces, drops, branch lines, feed mains, riser nipples, cross mains

methods include: flanged, soldered, welded, grooved, threaded joints

auxiliary devices include: water motor gongs, excess pressure pumps, signalling devices

alarm valve trim includes: alarm test valves, main drains, pressure gauges

signage and identification include: data plates, component identification, drain list

 

Knowledge

Learning Outcomes

Learning Objectives

D-13.01.01L

demonstrate knowledge of wet pipe systems, and their operation and characteristics define terminology associated with wet pipe systems

  identify hazards and describe safe work practices pertaining to wet pipe systems

  interpret codes, standards and regulations pertaining to wet pipe systems

  interpret information pertaining to wet pipe systems found on drawings and specifications

  identify tools and equipment relating to wet pipe systems, and describe their applications and procedures for use

  identify types of wet pipe systems and describe their operating principles and characteristics

  identify wet pipe system components and describe their location, purpose and operation

  identify alarm valves to be trimmed and describe their components and relevant design characteristics

  determine characteristics and application of sprinklers

  identify design criteriaa for wet pipe systems

  identify drainage requirements for each water-based system

D-13.01.02L

demonstrate knowledge of the procedures used to install wet pipe systems and components describe the procedures used to lay out and install wet pipe systems and components

describe the procedures used to install alarm valve trim

identify the factors to consider and requirements for installing auxiliary drains on wet pipe systems

describe the preventative methods used to prevent false alarms

identify the requirements for pressure testing of wet pipe systems and describe the associated procedures

describe methods used to prevent freezing

Range of Variables

types of wet pipe systems are only tree, gridded, looped

components include: fire department connection, test connections and drains, sprinklers, alarm devices, control valves, alarm check valves, water flow alarm devices, relief valves, valves, flow switches, riser manifolds, air vents

design criteria includes: density, square footage, occupancy classifications

D-13.02 Installs dry pipe systems

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-13.02.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-13.02.02P

determine and measure locations and grades for main and branch lines locations and grades for main and branch lines are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.02.03P

determine and measure locations and requirements of components locations and requirements of components are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.02.04P

determine and measure locations of auxiliary drains and requirements for valves locations of auxiliary drains and requirements for valves are determined and measured according to NFPA standards to ensure accessibility for servicing, testing and winterizing

D-13.02.05P

identify devices devices are identified according to NFPA standards in installation locations that are subject to freezing

D-13.02.06P

measure and install return bends and flexible drops return bends and flexible drops on dry pipe systems are measured and installed according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.02.07P

connect piping to water supply piping is connected to water supply using methods according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.02.08P

install auxiliary devices auxiliary devices are installed according to NFPA standards to ensure accessibility for servicing, testing and winterizing

D-13.02.09P

measure and install dry pipe valves and associated trim dry pipe valves and associated trim are measured and installed according to manufacturers’ specifications and NFPA standards

D-13.02.10P

determine system capacity system capacity of dry pipe systems is determined according to NFPA standards

D-13.02.11P

perform calculations calculations are performed according to NFPA standards on the required fill–time of compressed air or nitrogen

D-13.02.12P

perform pressure tests pressure tests are performed according to NFPA standards and AHJ

Range of Variables

components include: fire department connections, test connections and drains, water flow alarm devices, control valves, dry pipe valves, regulated air supply, regulated nitrogen supply, valves, quick opening devices (QODs), anti-flooding devices, auxiliary drains, drum drips, high/low supervisory devices, pressure gauges

devices include: dry pendant sprinklers, approved gaskets, air dryers

methods include: flanged, brazed, welded, grooved, threaded joints

trim includes: low air pressure switches, QODs, air maintenance devices

 

Knowledge

Learning Outcomes

Learning Objectives

D-13.02.01L demonstrate knowledge of dry pipe systems, their operation and characteristics define terminology associated with dry pipe systems
identify hazards and describe safe work practices pertaining to dry pipe systems
interpret codes, standards and regulations pertaining to dry pipe systems
interpret information pertaining to dry pipe systems found on drawings and specifications
identify tools and equipment relating to dry pipe systems, and describe their applications and procedures for use
identify types of dry pipe systems, and describe their operating principles and characteristics
identify dry pipe system components, and describe their locations, purpose and operation
D-13.02.02L demonstrate knowledge of the procedures used to install dry pipe systems and their components identify dry pipe valves to be trimmed, and describe their components and design characteristics
identify the factors to consider and requirements for installing auxiliary drains on dry pipe systems
identify the requirements for pressure testing of dry pipe systems and describe the associated procedures
describe the procedures used to lay out and install dry pipe systems and components
describe the procedures used to install dry pipe valve trim
describe the preventative methods used to prevent false alarms
identify calculations pertaining to capacity of dry pipe systems and air or nitrogen supply

Range of Variables

types of dry pipe systems are tree and looped

components include: fire department connections, test connections and drains, water flow alarm devices, control valves, dry pipe valves, regulated air supply, regulated nitrogen supply, valves, QODs, anti–flooding devices, auxiliary drains, drum drips, high/low supervisory devices, pressure gauges

preventative methods include: use of air and nitrogen supply, air dryer, air maintenance device

D-13.03 Installs antifreeze systems

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-13.03.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-13.03.02P

determine and measure locations of main and branch lines locations of main and branch lines are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.03.03P

determine and measure locations and requirements of components locations and requirements of components are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.03.04P

determine and measure locations of auxiliary drains and requirements for valves locations of auxiliary drains and requirements for valves are determined and measured according to NFPA standards to ensure accessibility for servicing and testing

D-13.03.05P

measure and fabricate piping piping is measured and fabricated for installation according to drawings, NFPA standards, AHJ and site conditions

D-13.03.06P

connect piping to water supply piping is connected to water supply using methods according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.03.07P

determine antifreeze strength antifreeze strength is determined according to NFPA guidelines and temperature of protected spaces and solution flammability restrictions by using refractometers

D-13.03.08P

install auxiliary devices auxiliary devices are installed according to NFPA standards to ensure accessibility for servicing and testing

D-13.03.09P

vent air air from system is vented at high point when filling system with antifreeze to prevent dilution of antifreeze by water

D-13.03.10P

determine system capacity system capacity of antifreeze system is determined according to NFPA standards

D-13.03.11P

perform pressure tests pressure tests are performed according to NFPA standards and AHJ

D-13.03.12P

install components components are installed to protect systems’ integrity

Range of Variables

components include: expansion tanks, RP, check valves

piping includes: risers, starter pieces, drops, branch lines, feed mains

methods include: flanged, soldered, welded, grooved, threaded joints

auxiliary devices include: flow switches, test points, fill cups

pressure tests include: hydrostatic, pneumatic testing

 

Knowledge

Learning Outcomes

Learning Objectives

D-13.03.01L demonstrate knowledge of antifreeze systems, their operation and characteristics define terminology associated with antifreeze systems
identify hazards and describe safe work practices pertaining to antifreeze systems
interpret codes, standards and regulations pertaining to antifreeze systems
interpret information pertaining to antifreeze systems found on drawings and specifications
identify tools and equipment relating to antifreeze systems, and describe their applications and procedures for use
identify the factors to consider for determining the need for freezing protection or antifreeze systems
identify types of antifreeze systems and their components, and describe their purpose and applications
    identify types and mixtures of antifreeze solutions, and describe their characteristics and applications
identify the requirements and describe the procedures used to handle, store and dispose of antifreeze
identify valves required for antifreeze systems
D-13.03.02L demonstrate knowledge of the procedures to install and maintain antifreeze systems identify installation requirements for antifreeze systems
describe the procedures used to lay out and install antifreeze systems
describe the procedures used to test and maintain antifreeze systems
identify the requirements for pressure testing of antifreeze systems, and describe the associated procedures

Range of Variables

factors include: location, accessibility, cost

types of antifreeze systems include: configuration, types of solutions, temperature mixtures

types and mixtures of antifreeze solutions include: used with potable water supply, used with non-potable water supply

installation requirements include: antifreeze loop, cross-connection control

D-13.04 Installs preaction/deluge systems

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-13.04.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-13.04.02P

determine and measure locations of main and branch lines locations of main and branch lines are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.04.03P

determine and measure locations and requirements of components locations and requirements of components are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.04.04P

determine and measure locations of auxiliary drains and requirements for valves locations of auxiliary drains and requirements for valves are determined and measured according to NFPA standards to ensure accessibility for servicing, testing and winterizing

D-13.04.05P

identify devices devices are identified according to NFPA standards in installation locations that are subject to freezing

D-13.04.06P

install preaction and deluge valves and trim preaction and deluge valves and trim are installed according to manufacturers’ specifications and NFPA standards

D-13.04.07P

install return bends and flexible drops on preaction and deluge systems return bends and flexible drops are installed on preaction and deluge systems according to NFPA standards to prevent plugging of sprinklers

D-13.04.08P

perform functional tests and meet intended design criteria functional tests are performed to verify operation of components and meet intended design criteria

D-13.04.09P

perform pressure tests pressure tests are performed according to NFPA standards and AHJ

Range of Variables

components include: fire department connections, test connections and drains, water flow alarm devices, control valves, preaction/deluge valves, regulated air supply, regulated nitrogen supply, valves, QODs, anti-flooding devices, auxiliary drains, high/low supervisory devices, pressure gauges

devices include: dry pendant sprinklers, flush seal gaskets and air dryers, detection devices

trim includes: solenoid actuators, diaphragm actuators

design criteria design criteria includes: interlock, double interlock, non-interlock, cross zoning

 

Knowledge

Learning Outcomes

Learning Objectives

D-13.04.01L demonstrate knowledge of preaction/deluge systems, their applications and operating principles define terminology associated with preaction/deluge systems
identify hazards and describe safe work practices pertaining to preaction/deluge systems
interpret codes, standards and regulations pertaining to preaction/deluge systems
interpret information pertaining to preaction/deluge systems found on drawings and specifications
identify tools and equipment relating to preaction/deluge systems, and describe their applications and procedures for use
identify types of preaction systemsand describe their operating principles and applications
identify types of deluge systems and describe their operating principles and applications
    identify trim components used on preaction/deluge valves, and describe their design variations and applications
identify types of alarms that a preaction/deluge valve will operate
identify supplemental fire detection systems, and describe their operating principles and applications;
    identify the system controls required for preaction/deluge systems
D-13.04.02L demonstrate knowledge of installation requirements and associated test procedures for preaction/deluge systems describe the procedures used to install system controls required for preaction/deluge systems
explain the requirements for drainage of preaction/deluge systems
describe the procedures used to lay out and install preaction/deluge systems
describe the procedures used to trim preaction/deluge valves
describe the procedures used to service and maintain preaction/deluge systems
identify the requirements for functional and pressure testing of preaction/deluge systems and describe the associated procedures

Range of Variables

types of preaction systems include: non–interlock, single interlock, double interlock

applications include: computer rooms, freezers, aircraft hangers, electrical rooms

types of deluge systems include: deluge, high–speed deluge

trim includes: solenoid actuators, diaphragm actuators

supplemental fire detection systems include: electric, pneumatic, hydraulic

D-13.05 Installs foam systems

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-13.05.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-13.05.02P

determine and measure locations of main and branch lines locations of main and branch lines are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.05.03P

determine and measure locations and requirements of components locations and requirements of components are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.05.04P

determine and measure locations of auxiliary drains and requirements for valves locations of auxiliary drains and requirements for valves are determined and measured according to NFPA standards to ensure accessibility for servicing and testing

D-13.05.05P

measure and fabricate piping piping is measured and fabricated for installation according to drawings, NFPA standards, AHJ and site conditions

D-13.05.06P

install foam tanks foam tanks are installed in close proximity to valves and to allow accessibility for refilling

D-13.05.07P

install valves and trim valves and trim are installed according to manufacturers’ specifications and NFPA standards

D-13.05.08P

install distribution devices distribution devices are installed according to manufacturers’ specifications and NFPA standards

D-13.05.09P

perform functional testing and meet intended design criteria functional tests are performed to verify operation of components and meet intended design criteria

D-13.05.10P

fill foam concentrate tanks foam concentrate tanks are filled according to manufacturers’ specifications using equipment

D-13.05.11P

perform pressure tests pressure tests are performed according to NFPA standards and AHJ

Range of Variables

components include: foam concentrate tanks, fire department connections, test connections and drains, water flow alarm devices, control valves, alarm/preaction/deluge valves, regulated air supply, regulated nitrogen supply, QODs, anti–flooding devices, auxiliary drains, high/low supervisory devices, pressure gauges

piping includes: risers, starter pieces, drops, branch lines, feed mains

valves and trim include: hydraulic and solenoid actuators, proportioners, diaphragm actuators

distribution devices include: sprinklers, foam generators, nozzles

design criteria includes: single interlock, double interlock, non–interlock and cross zoning, wet, deluge

equipment includes: positive displacement pumps, siphons

 

Knowledge

Learning Outcomes

Learning Objectives

D-13.05.01L demonstrate knowledge of foam systems, their applications and operating principles define terminology associated with foam systems
identify hazards and describe safe work practices pertaining to foam systems
interpret codes, standards and regulations pertaining to foam systems
interpret information pertaining to foam systems found on drawings and specifications
identify tools and equipment relating to foam systems, and describe their applications and procedures for use
identify types of foam systems and describe their operating principles and applications
identify the system controls required for foam systems
    identify types of concentrate used in foam systems and describe their characteristics and applications
identify supplemental fire detection systems, and describe their operating principles and applications
D-13.05.02L demonstrate knowledge of installation requirements and associated test procedures for foam systems describe the procedures used to lay out and install foam systems and components
    describe the installation requirements of foam systems
describe the procedures used to fill foam concentrate tanks
explain the requirements for drainage of the system
explain the operation of a balanced pressure proportioning system
describe the procedures used to trim foam systems
explain the operation of a pressure proportioning tank with and without bladder
describe the procedures used to test and maintain foam systems
identify the requirements for pressure testing of foam systems and describe the associated procedures

Range of Variables

hazards include: environmental considerations, containment, disposal

applications include: aircraft hangers, fuel storage tanks, chemical manufacturing and storage facilities

supplemental fire detection systems include: electric, pneumatic, hydraulic

installation requirements include: materials, hangers, supports and bracing, system actuation, testing, manufacturers’ specifications

D-13.06 Installs standpipe systems

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-13.06.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-13.06.02P

determine and measure location of piping and valves location of piping and valves are determined and measured to allow for accessibility according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.06.03P

determine and measure locations and requirements of components locations and requirements of components are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.06.04P

determine and measure fire hose valve locations fire hose valve locations are determined and measured according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.06.05P

install fire hose valve fire hose valve is installed with thread pattern that is compatible with the local fire department jurisdictional area

D-13.06.06P

install pressure reducing devices pressure reducing devices are installed to limit pressure according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.06.07P

install stand–alone standpipe and combination standpipe systems stand–alone standpipe and combination standpipe systems are installed according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.06.08P

install temporary standpipe systems temporary standpipe systems are installed to ensure fire protection during construction, according to drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.06.09P

perform pressure test pressure tests are performed according to NFPA standards and AHJ

Range of Variables

valves include: pressure reducing valves, pressure restricting valves, control valves, fire hose valves, check valves, alarm valves, preaction/deluge valves

components include: fire department connections, drains, control valves, regulated air supply, QODs, auxiliary drains, high/low supervisory devices, pressure gauges, hose valves, pressure regulating devices

 

Knowledge

Learning Outcomes

Learning Objectives

D-13.06.01L demonstrate knowledge of standpipe and hose systems, their applications and operating principles define terminology associated with standpipe and hose systems
identify hazards and describe safe work practices pertaining to standpipe and hose systems
interpret codes, standards and regulations pertaining to standpipe and hose systems
interpret code requirements pertaining to flushing connections in piping systems
interpret information pertaining to standpipe and hose systems found on drawings and specifications
identify tools and equipment relating to standpipe and hose systems, and describe their applications and procedures for use
identify the classes of standpipe systems, and describe their characteristics and applications
    identify types of standpipe systems, and describe their operating principles, characteristics and applications
identify the factors to consider and the requirements to determine standpipe system design
    identify types of hoses, hose valves and associated fittings, and describe their characteristics and applications
    identify types of hose cabinets and hose stations
identify types of hose spray nozzles and describe their applications
D-13.06.02L demonstrate knowledge of installation requirements and associated test procedures for standpipe systems describe the procedures used to lay out standpipe and hose systems
describe the procedures used to install hose cabinets and stations, and associated equipment
describe the procedures used to install hose spray nozzles
describe the procedures used to test and maintain standpipe systems
identify the requirements for pressure testing of standpipe and hose systems and describe the associated procedures

Range of Variables

classes of standpipe systems include: class I, class II, class III

types of standpipe systems include: wet pipe, dry pipe, manual, automatic, combined, semi–automatic dry

factors to consider for system design include: pipe sizing, flow rate, pressures, hose valve location, hose thread connection, AHJ, gauge location

D-13.07 Installs water mist and hybrid systems

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-13.07.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-13.07.02P

determine and measure location of piping and valves location of piping and valves are determined and measured according to manufacturers’ specifications, drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.07.03P

determine and measure locations and requirements of components locations and requirements of components are determined and measured according to manufacturers’ specifications, drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.07.04P

measure and fabricate piping piping is measured and fabricated for installation according to drawings, NFPA standards, AHJ and site conditions

D-13.07.05P

connect piping to water supply piping is connected to water supply using methods according to manufacturers’ specifications, drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.07.06P

install auxiliary devices auxiliary devices are installed according to NFPA standards to ensure accessibility for servicing and testing

D-13.07.07P

flush system system is flushed to prevent plugging of nozzles according to manufacturers’ specifications, drawings, project specifications, site conditions, AHJ and NFPA standards

D-13.07.08P

perform functional tests and meet intended design criteria functional tests are performed to verify operation of components and meet intended design criteria

D-13.07.09P

perform pressure tests pressure tests are performed according to NFPA standards and AHJ

Range of Variables

components include: positive displacement pumps, relief valves, detection devices and nozzles, nitrogen cylinders, water tanks

piping includes: risers, starter pieces, drops, branch lines, feed mains

methods include: flanged, welded, grooved, threaded, compression

auxiliary devices include: nozzles, emitters

design criteria includes: manufacturers’ discharge, time limitations

 

Knowledge

Learning Outcomes

Learning Objectives

D-13.07.01L demonstrate knowledge of water mist and hybrid systems, their applications and operating principles define terminology associated with water mist and hybrid systems
identify hazards and describe safe work practices pertaining to water mist and hybrid systems
interpret codes, standards and regulations pertaining to water mist and hybrid systems
interpret information pertaining to water mist and hybrid systems found on drawings and specifications
identify tools and equipment relating to water mist and hybrid systems, and describe their applications and procedures for use
identify types of water mist and hybrid systems, and describe their operating principles, characteristics and applications
D-13.07.02L demonstrate knowledge of installation requirements for water mist and hybrid systems describe the procedures used to lay out and install water mist and hybrid systems and components
    identify system controls for water mist and hybrid systems and their installation requirements
explain the requirements for drainage of water mist and hybrid systems
    identify the requirements for pressure testing of water mist and hybrid systems and describe the associated procedures

Range of Variables

types of water mist and hybrid systems include: single fluid, twin fluid, high pressure, medium pressure, low pressure

installation requirements include: materials, supports and hangers, system actuation, testing, manufacturers’ specifications/training, handling and storage

Task D-14 Installs specialty fire suppression systems

Task Descriptor

Thinking, Document Use, Numeracy

D-14.01 Installs dry and wet chemical, clean agent and carbon dioxide systems

Essential Skills

Specialty fire suppression systems are designed to extinguish a fire rather than control it. They have a finite supply of extinguishing agent and must be refilled after activation. These systems require a degree of specialization and unique skill sets among sprinkler fitters.

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

no

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-14.01.01P

select pipe and fittings pipe and fittings are selected to match manufacturers’ specifications

D-14.01.02P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-14.01.03P

remove possible obstructions possible obstructions are removed in pipe by reaming, cleaning and blowing out

D-14.01.04P

install clamps clamps are installed to prevent pipe movement during discharge of extinguishing agent according to NFPA standards

D-14.01.05P

measure and fabricate piping piping is measured and fabricated to meet site conditions

D-14.01.06P

measure and modify system piping system piping is measured and modified according to manufacturers’ specifications and site conditions

D-14.01.07P

install piping and nozzles piping and nozzles are installed according to drawings and specifications to ensure equal discharge, and according to NFPA standards

D-14.01.08P

install and secure storage cylinders storage cylinders are installed and secured to ensure safety due to high pressure of cylinders, according to manufacturers’ specifications and NFPA standards

D-14.01.09P

install activation devices activation devices are installed according to manufacturers’ specifications and NFPA standards

D-14.01.10P

pressure test system system is pressure tested according to manufacturers’ specifications

D-14.01.11P

assist in verification controls and actuators are verified by qualified personnel

Range of Variables

manufacturers’ specifications include: extra heavy fittings, pipe size, seamless pipe

tools and equipment include: swabs, acetone, rags

 

Knowledge

Learning Outcomes

Learning Objectives

D-14.01.01L demonstrate knowledge of wet and dry chemical, clean agent and carbon dioxide systems and their operation and characteristics define terminology associated with wet and dry chemical, clean agent and carbon dioxide systems
interpret information pertaining to wet and dry chemical, clean agent and carbon dioxide systems found on drawings and specifications
identify tools and equipment relating to wet and dry chemical, clean agent and carbon dioxide systems, and describe their applications and procedures for use
identify types of wet and dry chemical, clean agent and carbon dioxide systems, and describe their characteristics, operation and applications
describe the operating principles and applications of wet and dry chemical, clean agent and carbon dioxide systems
describe fixed pipe systems
    identify the components of wet and dry chemical, clean agent and carbon dioxide systems and describe their purpose and operation
    explain the properties of carbon dioxide
identify the extinguishing properties of wet and dry chemical, clean agent and carbon dioxide systems
    describe the procedures used to calculate the quantity of carbon dioxide extinguishing agent required for a system
    identify the factors to consider and limitations pertaining to halon systems
    identify types of pipe used for specialty fire suppression systems
    identify clean agent system media and their properties
    identify containment requirements for clean agent systems
    define the limited extinguishing ability of clean agent and carbon dioxide systems
    identify applications of clean agent and carbon dioxide systems
    identify hazards and describe safe work practices pertaining to wet and dry chemical, clean agent and carbon dioxide systems
D-14.01.02L demonstrate knowledge of installation of wet and dry chemical, clean agent and carbon dioxide systems identify the installation requirements for wet and dry chemical, and carbon dioxide systems and components
    interpret codes, standards, regulations and manufacturers’ specifications pertaining to wet and dry chemical, clean agent and carbon dioxide systems
    describe the procedures used to install wet and dry chemical, clean agent and carbon dioxide systems and components
D-14.01.03L demonstrate knowledge of inspection, and testing of wet and dry chemical, clean agent and carbon dioxide systems identify the requirements of inspection and acceptance testing of wet and dry chemical, clean agent and carbon dioxide systems
  explain the liabilities and responsibilities for the inspection and testing of wet and dry chemical, clean agent and carbon dioxide systems
D-14.01.04L demonstrate knowledge of procedures used to service, maintain and remove wet and dry chemical, clean agent and carbon dioxide systems describe the procedures used to service, maintain and remove wet and dry chemical, clean agent and carbon dioxide systems

Range of Variables

tools and equipment include: swabs, acetone, rags

types of carbon dioxide systems include: low pressure, high pressure

fixed pipe systems include: total flooding, local application

components include: for carbon dioxide system (alarms and indicators, life safety provisions, discharge nozzles, piping and fittings, supports, tanks and manifolds, release mechanisms, detection devices);
for clean agent system (alarms and indicators, life safety provisions, discharge nozzles, piping and fittings, supports, tanks and manifolds, release mechanisms, detection devices, pressure relief venting)

applications include: server rooms, archival storage, libraries, manufacturing facilities

hazards include: handling of materials and cylinders, accidental discharge

D-14.02 Installs portable extinguishers

Essential Skills

Document Use, Numeracy, Thinking

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-14.02.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work and manufacturers’ specifications

D-14.02.02P

determine type and location of extinguisher type and location of extinguisher is determined according to drawings, specifications and AHJ

D-14.02.03P

install extinguisher and cabinets extinguisher and cabinets are installed according to drawings, NFPA standards and AHJ

D-14.02.04P

confirm that extinguishers are fully charged extinguishers are confirmed to be fully charged with pins and seals in place along with a currently dated inspection tag which is stamped by qualified personnel

 

Knowledge

Learning Outcomes

Learning Objectives

D-14.02.01L demonstrate knowledge of procedures and requirements to install portable fire extinguishers define terminology associated with portable fire extinguishers
identify hazards and describe safe work practices pertaining to portable fire extinguishers
interpret codes, standards and regulations pertaining to portable fire extinguishers
interpret information pertaining to portable fire extinguishers found on drawings and specifications
identify tools and equipment relating to portable fire extinguishers, and describe their applications and procedures for use
identify classes and types of portable fire extinguishers, and describe their characteristics, operation and applications
    identify the components of portable fire extinguishers
    identify the installation requirements and procedures for portable fire extinguishers and cabinets
identify installation locations for portable fire extinguishers
    describe the procedures used to operate portable fire extinguishers
    explain the liabilities and responsibilities for the installation of portable fire extinguishers

Range of Variables

types of portable fire extinguishers include: wet and dry chemical, carbon dioxide, water-based, clean agent

installation locations include: cabinet, wall mount, wheeled

Task D-15 Installs detection devices

Task Descriptor

These devices detect a fire situation and initiate a response of the fire protection system. The installation of electrical detection systems is performed by sprinkler fitters in some jurisdictions.

D-15.01 Installs wet and dry pilot lines

Essential Skills

Document Use, Thinking, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-15.01.01P

identify pilot line and pilot line detector pilot line and pilot line detectors are identified according to temperature requirements for wet and dry pilot lines

D-15.01.02P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-15.01.03P

install pilot lines pilot lines are installed according to parameters

D-15.01.04P

space pilot line and fixed temperature HADs pilot line and fixed temperature HADs are spaced according to NFPA standards and manufacturers’ specifications

D-15.01.05P

connect pilot lines pilot lines are connected to valve trim according to manufacturers’ specifications

D-15.01.06P

perform pressure test pressure test for pilot lines is performed according to NFPA standards

Range of Variables

parameters include: proximity to sprinklers on fire protection piping, heat collection and ceiling structure, spacing of pilot line detectors, sizing and installation methods

 

Knowledge

Learning Outcomes

Learning Objectives

D-15.01.01L demonstrate knowledge of the procedures used to install, test and maintain wet and dry pilot lines and their associated pilot line detectors define terminology associated with wet and dry pilot lines
identify hazards and describe safe work practices pertaining to wet and dry pilot lines
interpret codes, standards and regulations pertaining to wet and dry pilot lines
interpret information pertaining to wet and dry pilot lines, found on drawings and specifications
identify tools and equipment relating to wet and dry pilot lines, and describe their applications and procedures for use
identify types of wet and dry pilot lines and their components, and describe their characteristics, parameters and applications
    describe the procedures used to install, test and maintain wet and dry pilot lines

D-15.02 Installs heat-actuated devices (HADs) (NOT COMMON CORE)

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

no

yes

NV

yes

no

yes

no

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-15.02.01P

determine location of HADs location of HADs is determined according to manufacturers’ specifications and AHJ

D-15.02.02P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-15.02.03P

mount releasing panel releasing panel is mounted in proximity to releasing devices to facilitate actuation of system

D-15.02.04P

install piping, tubing and wire piping, tubing and wire are installed in area being protected according to manufacturers’ specifications, AHJ and NFPA standards

D-15.02.05P

attach linear heat detection wire linear heat detection wire is attached according to manufacturers’ specifications

D-15.02.06P

test HADs HADs are tested according to manufacturers’ specifications

Range of Variables

HADs include: fixed temperature, rate of rise detectors, linear heat detectors

 

Knowledge

Learning Outcomes

Learning Objectives

D-15.02.01L demonstrate knowledge of the procedures used to install, test and maintain HADs and their associated components define terminology associated with HADs
identify hazards and describe safe work practices pertaining to HADs
interpret codes, standards and regulations pertaining to HADs
interpret information pertaining to HADs, found on drawings and specifications
identify tools and equipment relating to HADs, and describe their applications and procedures for use
identify types of HADs and describe their characteristics, parameters and applications
    describe the procedures used to install, test and maintain HADs

Range of Variables

types of HADs include: fixed temperature, rate of rise detectors, linear heat detector

parameters of HADs include: spacing, temperature, type

D-15.03 Installs spark detection systems (NOT COMMON CORE)

Essential Skills

Numeracy, Document Use, Thinking

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

no

yes

NV

yes

yes

no

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-15.03.01P

determine location of system location of system is determined according to manufacturers’ specifications, site conditions, NFPA standards and AHJ

D-15.03.02P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-15.03.03P

fasten spark detector to structure spark detector is fastened to structure to ensure detection of sparks and flame, and to prevent movement

D-15.03.04P

assemble system components system components are assembled according to manufacturers’ specifications, NFPA standards and AHJ

D-15.03.05P

install piping piping is installed to spark detection system according to manufacturers’ specifications, NFPA standards and AHJ

D-15.03.06P

verify operation operation is verified and calibrated according to site conditions, manufacturers’ specifications and AHJ

Range of Variables

components include: solenoids, nozzles, spark detector sensors

 

Knowledge

Learning Outcomes

Learning Objectives

D-15.03.01L demonstrate knowledge of the procedures used to install, test and maintain spark detection systems and their associated components define terminology associated with spark detection systems
identify hazards and describe safe work practices pertaining to spark detection systems
interpret codes, standards and regulations pertaining to spark detection systems
interpret information pertaining to spark detection systems, found on drawings and specifications
identify tools and equipment relating to spark detection systems, and describe their applications and procedures for use
identify types of spark detection systems and their components and describe their characteristics, parameters and applications
    describe the procedures used to install, test and maintain spark detection systems

Range of Variables

components include: solenoids, nozzles, spark detectors

parameters of spark detection systems include: spacing, location

D-15.04 Installs air sampling systems (NOT COMMON CORE)

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

no

yes

NV

yes

yes

no

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-15.04.01P

determine location of system location of system is determined according to drawings, site conditions and manufacturers’ specifications

D-15.03.02P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-15.04.03P

connect components components of air sampling system are connected according to manufacturers’ specifications and AHJ

D-15.04.04P

install air sampling pipe air sampling pipe is installed to detect particulate concentration in area of application according to manufacturers’ specifications and AHJ

D-15.04.05P

connect and terminate air sampling system air sampling system is connected to, and terminated from sampling/activation panel according to manufacturers’ specifications and AHJ

 

Knowledge

Learning Outcomes

Learning Objectives

D-15.04.01L demonstrate knowledge of the procedures used to install, test and maintain air sampling systems and their associated components define terminology associated with air sampling systems
identify hazards and describe safe work practices pertaining to air sampling systems
interpret codes, standards and regulations pertaining to air sampling systems
interpret information pertaining to air sampling systems, found on drawings and specifications
identify tools and equipment relating to air sampling systems, and describe their applications and procedures for use
identify types of air sampling systems and describe their characteristics, parameters and applications
    describe the procedures used to install, test and maintain air sampling systems

Range of Variables

components include: sampling/activation panels, tubing, sampling point

D-15.05 Installs electrical detection systems (NOT COMMON CORE)

Essential Skills

Thinking, Document Use, Numeracy

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

no

no

no

yes

NV

yes

no

no

no

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-15.05.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-15.05.02P

install smoke and heat detectors smoke and heat detectors are installed according to job and site requirements, manufacturers’ specifications and AHJ

D-15.05.03P

verify operation of smoke and heat detectors and ensure connections operation of smoke and heat detectors are verified according to manufacturers’ specifications, codes and standards and AHJ

Range of Variables

codes and standards include: Canadian Standards for Fire Alarm Systems (CAN/ULC), NFPA standards

 

Knowledge

Learning Outcomes

Learning Objectives

D-15.05.01L demonstrate knowledge of the procedures used to install, test and maintain electrical detection systems and their associated components define terminology associated with electrical detection systems
identify hazards and describe safe work practices pertaining to electrical detection systems
interpret codes, standards and regulations pertaining to electrical detection systems
interpret information pertaining to electrical detection systems, found on drawings and specifications
identify tools and equipment relating to electrical detection systems, and describe their applications and procedures for use
identify types of electrical detection systems and describe their characteristics, parameters and applications
    describe the procedures used to install, test and maintain electrical detection systems

Range of Variables

components include: smoke detectors, heat detectors, releasing panels

codes and standards include: CAN/ULC, NFPA standards

types of electrical detection systems include: single zone, cross zone, addressable, conventional

Task D-16 Installs signal-initiating devices

Task Descriptor

Alarm–initiating devices provide electrical signals to the local alarms which warn of the activation of the fire protection system. Supervisory initiating devices provide notification of trouble or impairment of the fire protection system.

D-16.01 Installs alarm-initiating devices

Essential Skills

Thinking, Document Use, Working with Others

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-16.01.01P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-16.01.02P

install device device is installed according to pipe size, system type and location to allow for replacement and repair according to site conditions, manufacturers’ specifications and AHJ

D-16.01.03P

determine location of alarm-initiating devices location of alarm-initiating devices is determined according to drawings and NFPA standards and manufacturers’ specifications

D-16.01.04P

attach devices to piping devices are attached to piping by methods according to manufacturers’ specifications

D-16.01.05P

install a means of testing a means of testing is installed according to manufacturers’ specifications, NFPA standards and AHJ

D-16.01.06P

verify operation of devices devices are field tested and adjusted according to manufacturers’ specifications, NFPA standards and AHJ

Range of Variables

methods include: using threaded connections, using clamps

testing includes: a test and drain valve or an alarm test valve, inspectors’ test connection

 

Knowledge

Learning Outcomes

Learning Objectives

D-16.01.01L demonstrate knowledge of the procedures used to install, test and maintain electrical detection systems and their associated components define terminology associated with electrical detection systems
identify hazards and describe safe work practices pertaining to electrical detection systems
interpret codes, standards and regulations pertaining to electrical detection systems
interpret information pertaining to electrical detection systems, found on drawings and specifications
identify tools and equipment relating to electrical detection systems, and describe their applications and procedures for use
identify types of electrical detection systems and describe their characteristics, parameters and applications
    describe the procedures used to install, test and maintain electrical detection systems

Range of Variables

types of alarm-initiating devices include: paddle–type flow switches, pressure switches

D-16.02 Installs supervisory-initiating devices

Essential Skills

Thinking, Document Use, Working with Others

NL

NS

PE

NB

QC

ON

MB

SK

AB

BC

NT

YT

NU

yes

yes

yes

yes

NV

yes

yes

yes

yes

yes

NV

NV

NV

 

Skills

Performance Criteria

Evidence of Attainment

D-16.02.01P

select supervisory–initiating device supervisory-initiating device is selected according to components being supervised, system type and location

D-16.02.02P

determine location of supervisory–initiating devices location of supervisory-initiating devices is determined according to site conditions, manufacturers’ specifications and drawings

D-16.02.03P

select and use tools and equipment tools and equipment are selected and used according to scope of work

D-16.02.04P

attach supervisory–initiating devices supervisory–initiating devices are attached to piping and components according to manufacturers’ specifications, site conditions and AHJ

D-16.02.05P

verify operation of supervisory–initiating devices supervisory-initiating devices are field tested and adjusted according to manufacturers’ specifications, NFPA standards, site conditions and AHJ

Range of Variables

supervisory-initiating devices include: low air pressure, low water pressure, tamper (switches)

 

Knowledge

Learning Outcomes

Learning Objectives

D-16.02.01L demonstrate knowledge of procedures and requirements to install, test and maintain supervisory–initiating devices define terminology associated with supervisory–initiating devices
identify hazards and describe safe work practices pertaining to supervisory–initiating devices
interpret codes, standards and regulations pertaining to supervisory–initiating devices
interpret information pertaining to supervisory–initiating devices, found on drawings and specifications
identify tools and equipment relating to supervisory–initiating devices, and describe their applications and procedures for use
identify types of supervisory–initiating devices and describe their characteristics, parameters and applications
    describe the procedures used to install, test and maintain supervisory-initiating devices
    describe the operation and applications of supervisory–initiating devices

Range of Variables

types of supervisory–initiating devices include: low air pressure, low water pressure, tamper (switches)